We usually perform being a tangible workforce making sure that we will give you the most beneficial excellent plus the finest selling price for Automatic Water Mist System, Fire Alarm System For Hazardous Locations, Fm Approved Water Mist System, Our tenet is clear all the time: to deliver high quality product at competitive price to customers around the world. We welcome potential buyers to contact us for OEM and ODM orders.
Newly Arrival Water Mist Systems Standards - High pressure water mist fire extinguishing system(2.1) – Anbesec Detail:

High-pressure plunger pump

1

High pressure plunger pump  is one of the core components of high pressure water mist system, our company high-pressure plunger pump adopts foreign advanced technology, it has the advantages of long service life and stable performance. Liquid end is made of brass production.

 

High-pressure plunger pump main technical parameters:

specifications

Flow rate(L/min)

Working pressure(Mpa)

power(KW)

Rotating speed

(r/min)

origin

HAWK-HFR80FR

80

28

42

1450

Italy

Pressure-stabilizing pump

2

The pressure stabilizing pump is to stabilize the pressure in the pipeline. After the zone valve is opened, the pipeline pressure is under The pressure stabilizing pump will start automatically. After running for more than 10 seconds, the pressure still cannot reach 16bar, automatically start the high-pressure main pump. The stabilizer pump is made of stainless steel.

 

 

Pump motor

水泵电机

Our company’s high-pressure water mist automatic fire extinguishing system adopts frequency conversion, speed-adjustable, three-phase asynchronous motor.

When selecting  high pressure water mist fire extinguishing system, the rated speed of the motor should meet the speed requirements of the pump, selection of the power of the motor should be based on the working pressure and the flow rate of the water pump.

N=2PQ*10-2

N—-Motor power(Kw);

O—–Working pressure of water pump(MPa);

P—-Flow of water pump(L/min)

High pressure water mist nozzle

4

 

The high-pressure water mist nozzle consists of the main body of the nozzle, the swirl core of the nozzle, and the nozzle main body, filter screen, filter screen sleeve, etc. Under certain water pressure, the water is atomized by centrifugation, impact, jet and other methods.

 

Community-verified icon

 

Technical parameters:

Specification model Rated flow rate(L/min) Minimum working pressure (MPa) Maximum installation distance (m) Height of installation (m)
XSWT0.5/10 5 10 3 According to the design specification
XSWT0.7/10 7 10 3
XSWT1.0/10 10 10 3
XSWT1.2/10 12 10 3
XSWT1.5/10 15 10 3

Pressure regulating relief valve

5

 

The pressure regulating relief valve is connected with the high-pressure water pump and the water tank, when the main pump pressure is too high, the discharged water can flow back to the storage tank. The pressure regulating relief valve is made of brass.

 

Safety relief valve

6

The pressure value of relief action of the safety relief valve is 16.8MPa, and the safety relief valve also known as safety overflow valve is an automatic pressure relief device driven by medium pressure. The safety relief valve is made of stainless steel.

 

Water storage tank

7

 

Stainless steel water storage tank ensure automatic water replenishment, and is equipped with a liquid level display device, low liquid level alarm device and overflow and  venting  device.

 


Product detail pictures:

Newly Arrival Water Mist Systems Standards - High pressure water mist fire extinguishing system(2.1)  – Anbesec detail pictures

Newly Arrival Water Mist Systems Standards - High pressure water mist fire extinguishing system(2.1)  – Anbesec detail pictures

Newly Arrival Water Mist Systems Standards - High pressure water mist fire extinguishing system(2.1)  – Anbesec detail pictures

Newly Arrival Water Mist Systems Standards - High pressure water mist fire extinguishing system(2.1)  – Anbesec detail pictures

Newly Arrival Water Mist Systems Standards - High pressure water mist fire extinguishing system(2.1)  – Anbesec detail pictures

Newly Arrival Water Mist Systems Standards - High pressure water mist fire extinguishing system(2.1)  – Anbesec detail pictures

Newly Arrival Water Mist Systems Standards - High pressure water mist fire extinguishing system(2.1)  – Anbesec detail pictures

Newly Arrival Water Mist Systems Standards - High pressure water mist fire extinguishing system(2.1)  – Anbesec detail pictures


Related Product Guide:

Our purpose is to fulfill our clients by offering golden company, great price and premium quality for Newly Arrival Water Mist Systems Standards - High pressure water mist fire extinguishing system(2.1) – Anbesec , The product will supply to all over the world, such as: Sri Lanka, Bangkok, Pretoria, Certainly, competitive price, suitable package and timely delivery will be assured as per customers' demands. We sincerely hope to build business relationship with you on the basis of mutual benefit and profit in the very near future. Warmly welcome to contact us and become our direct cooperators.
This manufacturer can keep improving and perfecting products and service, it is in line with the rules of market competition, a competitive company.
5 Stars By Alexander from Anguilla - 2018.06.03 10:17
The product manager is a very hot and professional person, we have a pleasant conversation, and finally we reached a consensus agreement.
5 Stars By Lisa from Ghana - 2017.10.27 12:12

Send your message to us: