We believe that long expression partnership is often a result of top of the range, value added service, prosperous encounter and personal contact for Water Mist System Components, Water Mist Fire Fighting System, Linear Heat Detector Cable, We always concertrating on developing new creative product to meet request from our clients all over the world. Join us and let's make driving safer and funnier together!
Low price for Rate Of Rise Linear Heat Detector - Linear Heat Detector NMS2001 Cable – Anbesec Detail:

MicroSenseWire Analog Linear Heat Detector –NMS2001, consists of four cores with high performance and good adaptability, is widely used in industrial, commercial, and other over-heat hazardous sites.

Structure and how it works

NMS2001 – LHD cable consists of four cores (red and white) twisting together, and the outer jacket is made from heat-resisting material—PVC, strengthening the durability and the reliability. The material of outer jacket can be changed in order to meet the requirements of different environments, chemical resistance material and anti-UV material.

The structure is shown below:

The NMS2001 – LHD cable has high performance of fire retardance, consists of four cores made from special insulating layer material–NTC (negative temperature coefficient). The terminal unit can indicate the change of system temperature through monitoring the change of resistance value.

During wire connection and installation, two parallel red cables and two parallel white cables are connected to control unit and terminal unit, formulating a loop circuit.

2
2132321

The system detects the resistance fluctuation of Linear Heat Detection Cable resulted from the fluctuation of circuit temperature–i.e. when temperature rises, resistance drops. This fluctuation is monitored through linear detector Control Unit of Linear Heat Detection Cable. When it reaches preset alarm threshold value, output alarming signal. This feature allows the system to have the ability to detect the fire in point or in line of whole circuit, which is that the system could detect the temperature fluctuation in certain point as well as certain area. After alarming, it could automatically restore to working condition.

General length of finished product is 500m per reel. Longer length is not recommended, due to the feature of analog signal. The alarm temperature is related to the length of LHD cable, so it is suggested to make the alarm test with 2m LHD cable. If the alarm temperature is set at 105℃, test with 5m LHD cable, the alarm temperature may be lower, on the contrary, the alarm temperature may be higher.

Features

♦ High adaptability: it could be applied in narrow areas , harsh and hazardous environments;

♦ Great compatibility: NMS2001-I Linear Detector Control Unit has relay output, which could be connected to various fire alarm control panel mainframes;

♦ Chemical resistance and abrasion resistance: extrude and make jacket with high-strength, which could meet different needs;

Re-settable: the LHD cable could automatically reset after alarming (under the situation of fire alarming temperature does not harm linear heat detection cable), saving much cost for maintenance and operation;

Multiple monitoring functions: except for normal fire alarm, fault of open circuit or short circuit;

♦ Good anti-EMI interference (Interruption resistance): four-core stranded structure has strong ability to resist electromagnetic field interruption, and

♦ Easy installation and maintenance.

FeaturesApplications

♦ Cable tray

♦ Conveyor belt

♦ Power distribution equipments: switch cabinet, transformer, transformer station and motor control center

♦ Dust collector and bag type dust collector

♦ Warehouse and rack storage

♦ Industrial material processing system

♦ Bridge, wharf and vessel

♦ Chemicals storage facilities

♦ Aircraft hangar and oil depot

NMS2001 system connection

523523

Notice:

1. It is suggested that terminal unit and connected fire alarm control panel shall be reliably grounded.

2. Forbid bending or turning the LHD cable with an acute angle, and the minimum bending radius of the LHD cable should not be less than 150mm preventing from damage.

3. The product shall be well packed during the shipment, forbidding damage.

4. It is suggested to test the detector annually, the normal resistance between the cores shall not be less than 50MΩ, otherwise, please replace. Test equipment: 500V megger.

5. It is not allowed to maintain the detector without contacting our company.


Product detail pictures:

Low price for Rate Of Rise Linear Heat Detector - Linear Heat Detector NMS2001 Cable  – Anbesec detail pictures


Related Product Guide:

We purpose to understand high quality disfigurement with the output and supply the top service to domestic and overseas buyers wholeheartedly for Low price for Rate Of Rise Linear Heat Detector - Linear Heat Detector NMS2001 Cable – Anbesec , The product will supply to all over the world, such as: Mombasa, Rwanda, Afghanistan, Our company will continue to adhere to the " superior quality, reputable, the user first " principle wholeheartedly. We warmly welcome friends from all walks of life to visit and give guidance, work together and create a brilliant future!
The factory technical staff not only have high level of technology, their English level is also very good, this is a great help to technology communication.
5 Stars By Josephine from Niger - 2018.10.31 10:02
The company can keep up with the changes in this industry market, product updates fast and the price is cheap, this is our second cooperation, it's good.
5 Stars By Afra from Mombasa - 2017.09.22 11:32

Send your message to us: