We have our own product sales staff, style crew, technical group, QC staff and package staff. We now have strict high quality management procedures for each approach. Also, all of our workers are experienced in printing subject for Linear Heat Detector System, Hi-Fog System For Data Center, Water Misting System Rentals, Our products enjoy good popularity among our customers. We welcome customers, business associations and friends from all parts of the world to contact us and seek cooperation for mutual benefits.
Factory source Fire Detector For Railway Station - Linear Heat Detector NMS2001 Cable – Anbesec Detail:

MicroSenseWire Analog Linear Heat Detector –NMS2001, consists of four cores with high performance and good adaptability, is widely used in industrial, commercial, and other over-heat hazardous sites.

Structure and how it works

NMS2001 – LHD cable consists of four cores (red and white) twisting together, and the outer jacket is made from heat-resisting material—PVC, strengthening the durability and the reliability. The material of outer jacket can be changed in order to meet the requirements of different environments, chemical resistance material and anti-UV material.

The structure is shown below:

The NMS2001 – LHD cable has high performance of fire retardance, consists of four cores made from special insulating layer material–NTC (negative temperature coefficient). The terminal unit can indicate the change of system temperature through monitoring the change of resistance value.

During wire connection and installation, two parallel red cables and two parallel white cables are connected to control unit and terminal unit, formulating a loop circuit.

2
2132321

The system detects the resistance fluctuation of Linear Heat Detection Cable resulted from the fluctuation of circuit temperature–i.e. when temperature rises, resistance drops. This fluctuation is monitored through linear detector Control Unit of Linear Heat Detection Cable. When it reaches preset alarm threshold value, output alarming signal. This feature allows the system to have the ability to detect the fire in point or in line of whole circuit, which is that the system could detect the temperature fluctuation in certain point as well as certain area. After alarming, it could automatically restore to working condition.

General length of finished product is 500m per reel. Longer length is not recommended, due to the feature of analog signal. The alarm temperature is related to the length of LHD cable, so it is suggested to make the alarm test with 2m LHD cable. If the alarm temperature is set at 105℃, test with 5m LHD cable, the alarm temperature may be lower, on the contrary, the alarm temperature may be higher.

Features

♦ High adaptability: it could be applied in narrow areas , harsh and hazardous environments;

♦ Great compatibility: NMS2001-I Linear Detector Control Unit has relay output, which could be connected to various fire alarm control panel mainframes;

♦ Chemical resistance and abrasion resistance: extrude and make jacket with high-strength, which could meet different needs;

Re-settable: the LHD cable could automatically reset after alarming (under the situation of fire alarming temperature does not harm linear heat detection cable), saving much cost for maintenance and operation;

Multiple monitoring functions: except for normal fire alarm, fault of open circuit or short circuit;

♦ Good anti-EMI interference (Interruption resistance): four-core stranded structure has strong ability to resist electromagnetic field interruption, and

♦ Easy installation and maintenance.

FeaturesApplications

♦ Cable tray

♦ Conveyor belt

♦ Power distribution equipments: switch cabinet, transformer, transformer station and motor control center

♦ Dust collector and bag type dust collector

♦ Warehouse and rack storage

♦ Industrial material processing system

♦ Bridge, wharf and vessel

♦ Chemicals storage facilities

♦ Aircraft hangar and oil depot

NMS2001 system connection

523523

Notice:

1. It is suggested that terminal unit and connected fire alarm control panel shall be reliably grounded.

2. Forbid bending or turning the LHD cable with an acute angle, and the minimum bending radius of the LHD cable should not be less than 150mm preventing from damage.

3. The product shall be well packed during the shipment, forbidding damage.

4. It is suggested to test the detector annually, the normal resistance between the cores shall not be less than 50MΩ, otherwise, please replace. Test equipment: 500V megger.

5. It is not allowed to maintain the detector without contacting our company.


Product detail pictures:

Factory source Fire Detector For Railway Station - Linear Heat Detector NMS2001 Cable  – Anbesec detail pictures


Related Product Guide:

Our enterprise since its inception, constantly regards product good quality as organization life, constantly improve production technology, strengthen merchandise high quality and continuously strengthen enterprise total good quality administration, in strict accordance with all the national standard ISO 9001:2000 for Factory source Fire Detector For Railway Station - Linear Heat Detector NMS2001 Cable – Anbesec , The product will supply to all over the world, such as: Marseille, Finland, Ecuador, We look forward to hearing from you, whether you are a returning customer or a new one. We hope you will find what you are looking for here, if not, please contact us immediately. We pride ourselves on top notch customer service and response. Thank you for your business and support!
  • The customer service staff's answer is very meticulous, the most important is that the product quality is very good, and packaged carefully, shipped quickly!
    5 Stars By Alva from Tunisia - 2017.12.19 11:10
    Perfect services, quality products and competitive prices, we have work many times, every time is delighted, wish continue to maintain!
    5 Stars By Belinda from New Zealand - 2017.04.08 14:55

    Send your message to us: